Technical description

  • Информационные материалы

    Информационные материалы

    Primary differential pressure devices are standardized mechanical flow sensors, often also referred to as differential pressure transducers. The primary differential pressure devices are calculated and manufactured according to DIN EN ISO 5167.

    Through constriction of the line diameter in the pressure device, the flow rate creates a differential pressure that is converted with the help of a differential pressure transmitter into a proportional current signal or flow value. The assignment of differential pressure to flow is created by means of a "calculation of the primary differential pressure device".

    Primary differential pressure devices are suitable for single-phase media such as gas, vapor and liquids without solid components.

    Requirement when ordering a primary differential pressure device

    Always quote the orifice plate calculation and the classification according to the pressure equipment directive 2014/68/EU (PED) when placing an order.

    Orifice plate calculation - calculation protocol

    For the "orifice plate calculation" service, you need to fill out the "Questionnaire for calculation of a primary differential pressure device according to DIN EN ISO 5167". The intelligent "SITRANS F O questionnaire online" can be found in the PIA Life Cycle Portal at http://www.siemens.com/pia-portal.

    For this purpose, you need to specify all the data of the measuring point, medium, process and pipe data, as well as details of installation conditions, flow conditions, permissible pressure losses and accuracy requirements.

    We will be unable to carry out the calculation if there are any data missing. A calculation protocol with a consecutive number documents the calculation of the orifice plate. We require this calculation protocol from the customer for manufacturing purposes. It is to be included in the order for the orifice plate.

    Important note:

    The "Orifice Plate Calculation with Preparation of a Calculation Protocol" service is a separate process, and must be carried out before the orifice plate is ordered.

    The calculation protocol issued by the customer is to be included in the order for the orifice plate.

    Classification in accordance with pressure equipment directive 2014/68/EU (PED)

    The pressure equipment directive must also be applied to the Orifice portfolio for use in Europe.

    In compliance with the pressure equipment directive, equipment is divided into categories I to III or Article 3 paragraph 3 according to danger potential (medium/pressure/volume/nominal diameter).

    Submission of this design data in accordance with pressure equipment directive 2014/68/EU is mandatory for ordering and manufacture, and must be specified by customers in the orifice plate order.

    The Order No. of the orifice plate contains the relevant Category I, II, III or Article 4 paragraph 3 in the order code.

    Detailed information is available under "Pressure equipment directive 2014/68/EU".

    How to order the "Orifice plate with appended calculation protocol" product

    To order an orifice plate, you need to supply the following data:

    • Complete Order No. of the orifice plate, including the respective order code "Manufacture according to pressure equipment directive":
      • Category I, II, III or Article 4 paragraph 3 and the design data with Order Codes Y31 to Y35
      • Or without (only available outside Europe!)
    • Appended "Calculation Protocol" issued by the customer with Order Code Y21 or Y22, or statement "Orifice plate without calculation" with Order Code Y01

    The orifice plate can only be manufactured when it has been passed as a "clean order", i. e. it has been confirmed that the data of the Order No. match the data of the calculation protocol.

    Область применения

    Power stations

    Measurement of steam, condensate and water.

    Petrochemical industry/Refineries

    Measurement of water, steam and liquid and gas hydrocarbons.

    Chemical industry

    Measurement of various liquid and gas media.

    Oil and gas industries

    Measurement of liquid and gas hydrocarbons.

    Дизайн

    Orifice plate with annular chambers

    The version orifice plate with annular chambers comprises two support rings which are connected to the inside of the pipe over an annular chamber and an annular gap. Tapping sockets direct the differential pressure from the support rings to the differential pressure transmitter over shut-off fittings and differential pressure lines.

    The orifice disk is inserted between the support rings together with a gasket.

    Orifice plate with single tappings

    In the version of the orifice plate with single tappings the orifice plate is a single unit. The inside of the tube is connected to the tapping sockets by two single tappings.

    Both types of orifice plate are installed between two flanges in the pipeline.

    Характеристика

    The orifice plate has a square-law relationship between differential pressure and flow. A square-root transmitter is required therefore to create a linear flow characteristic.

    Relationship between flow q and differential pressure Δp

    Функции

    Mode of operation

    The orifice plate creates a differential pressure. The pressure is transferred through the vertical columns of medium in the differential pressure lines to the measuring cell of the differential pressure transmitter. The transmitter converts the pressure signal with square-root characteristic into a flow-proportional current or into a digital signal, e. g. PROFIBUS.

    Types of primary differential pressure devices

    Shapes of the orifice disk aperture

    The primary differential pressure devices are calculated and manufactured according to DIN EN ISO 5167. According to this, the application range of the standard orifice disk aperture form A is limited by the Reynolds number. The limits depend on the diameter ratio β = d/D. (D: internal diameter of pipe).

    In the case of Reynolds numbers from approx. 500 to 2.5 x 105 and DN 40 to DN 150, the orifice disk aperture form B (quarter circle) can be used for slightly less accurate measurements. The profile radius r depends on the diameter ratio ß and results from the calculation of the diameter of the orifice disk aperture d.

    The cylindrical orifice disk aperture form D is used for measurements in both flow directions.

    Tapping sockets

    Type of threaded connections and welding connections dependent on the measured medium and the nominal pressure of the shut-off fitting

    The type of socket connections depends on the measured medium and the nominal pressure of the shut-off fittings; the socket length depends on the nominal diameter (pipe diameter) of the primary differential pressure device and the operating temperature (because of the thermal insulation!). The socket position depends on the measured medium and the flow direction.

    • With threaded connection G½ DIN ISO 228/1, connection dimensions to DIN 19207 Form V, for liquids and gases up to PN 160, for steam up to PN 100
    • With threaded connection ½-14 NPT male, for version acc. to ASME up to class 600
    • With Ø 12 mm pipe connection for pipe union with ferrule
    • With Ø 21.3 mm welding connection for liquids and gases up to PN 400, and for steam up to PN 100, or Ø 24 mm for liquids and gases over PN 400, and for steam over PN 100

    Other connections on request.

    Length of tapping sockets

    The length of the tapping sockets are specified in DIN 19205, Part 2.

    If using with high temperatures and stronger insulations, please quote the insulation thickness and the required length of the tapping sockets when placing an order.

    Threaded connections of tapping sockets for liquids and gases up to PN 160, for steam up to PN 100, dimensions in mm

    Threaded connection ½-14 NPT male, dimensions in mm

    With Ø 12 mm pipe for pipe union with ferrule, dimensions in mm

    Welding connections of tapping sockets, dimensions in mm

    Position of the tapping sockets

    When measuring liquids and gases, the position of the tapping sockets must comply with the tables according to DIN 19205; when measuring steam, the compensation vessels must be at the same height.

    • Horizontal steam lines

    Horizontal steam line in front of a wall with primary differential pressure device and valve combination; with annular chamber orifice plate or single part orifice plate with special length of 65 mm

    In the case of horizontal steam lines, straight sockets are arranged opposite each other or, if the pipe is close to a wall, with bent sockets on one side.

    • Vertical steam lines

    Vertical steam line with primary differential pressure device and valve combination

    In the case of vertical and inclined steam lines, the lower socket is bent upwards so that the connection flanges and compensation vessels are also at the same height.

    Extract from DIN 19205, Part 1, August 1988

    No.

    Pipe position and flow direction

    Position of the tapping sockets

     

    Application

    1

    Horizontal

    180°

     

    With compensation vessels

    2 1)2)

     

    3 1) 2)

     

    4

    Vertical

    Rising

    90°

     

    5

    Setpoint direction falling

    6

    Rising

    180°

     

    7

    Setpoint direction falling

    10

    Horizontal

    <γ ³)

     

    Without compensation vessels

    11

    Horizontal, vertical

    → ↓ ↑

    180°

     

    13

    Vertical

    ↓ ↑

    90°

     


    1) Not possible with orifice plates with single tappings (overall length 40 mm). Special length of 65 mm is possible.

    ²) Only possible with orifice plates with annular chambers (overall length 65 mm) with bent tapping sockets.

    ³) Angle γ is dependent on the nominal pressure and nominal diameter in accordance with DIN 19 205.

    Principle of the differential pressure method

    Principle of the differential pressure method: Pressure curve at a pipe restriction

    A primary differential pressure device is installed at the measuring point to measure the flow. This restricts the pipe and has two connections for sampling the differential pressure. If the properties of the primary device and the medium are known such that the equation below can be evaluated, the differential pressure is a measure of the absolute flow. No reference measurements are required; the flow measurement can be checked independent of the device manufacturer.

    The differential pressure method is based on the law of continuity and Bernoulli’s energy equation.

    According to the law of continuity, the flow of a moving medium in a pipeline is the same at all points. If the cross-section is reduced at one point, the flow velocity must increase at this point. According to Bernoulli’s energy equation, the energy content of a flowing medium is constant and is the total of the static (pressure) and kinetic (movement) energies. An increase in the flow rate therefore results in a reduction in the static pressure (see the figure "Principle of the differential pressure method: Pressure curve at a pipe restriction"). This pressure difference Δp, the so-called differential pressure, is a measure of the flow.

    In general the following equation applies: q = c√Δp

    Where:

    • q: flow (qm, qv) mass flow or volume flow
    • Δp: Differential pressure
    • c: Factor depending on the dimensions of the pipeline, the type of constriction, the density of the flowing medium etc.

    According to this equation, the differential pressure created by the constriction is proportionally equal to the square of the flow (see the figure "Relationship between flow q and differential pressure Δp").

    Интеграция

    The orifice plate is installed between two flanges in the pipeline. Using compensation vessels (for steam) and initial shut-off valves, the differential pressure of the high-pressure side and low-pressure side is directed through differential pressure lines to a multiple valve manifold and on to the differential pressure transmitter. For media with extreme pressure and temperature fluctuations it makes sense to take an additional measurement of the pressure and temperature in order to correct the flow signal of the transmitter in a subsequent correction computer.

    Selection of mounting point

    The flow measuring regulations DIN EN ISO 5167 not only consider the design of primary differential pressure devices, but also assume that their installation is in accordance with the standard so that the specified tolerances can be retained. The required inlet and outlet pipe sections according to ISO 5167 can be found in the calculation protocol of the respective orifice plate. Configuration of the pipeline should allow for standardized installation (required inlet and outlet pipe section). Particular attention must be paid to ensure that the primary device can be fitted in a sufficiently long straight section of pipe. Bends, valves and similar should be fitted sufficiently far upstream of the primary device to prevent them having a detrimental effect. Primary devices with a large diameter ratio are particularly sensitive to interferences.

    Design of measuring point

    The design of the measuring point depends on the medium and on the spatial conditions. The designs for gas and water only differ with regard to the position of the tapping sockets (see the figure "Measuring setup"); compensation vessels must also be provided for steam.

    Metering pipes

    On lines with small nominal diameters (DN 10 to DN 50) the measurements are influenced by the wall roughness and diameter tolerances of the pipes, far more so than by large nominal diameters. These influences are counteracted by using metering pipes with fitting inlet and outlet pipe sections made of precision pipes. For exact measurements with metering pipes, the flow coefficient C needs to be determined by means of calibration.

    Design of measuring point, example: gas measurement (non-corrosive, non-hazardous)

    Measuring setup

    Особенности

    • Primary differential pressure devices are suitable for universal use across the globe.
    • Primary differential pressure devices are very robust and can be used in a wide range of nominal diameters.
    • Suitable for high temperature and pressure ranges.
    • No wet calibration required as they use an internationally standardized flow rate measurement procedure.
    • The differential pressure transmitter can be used over a long distance from the measuring location.
    • The differential pressure method is well known and has a large installed base.
    • The SITRANS P differential pressure transmitter is easy to parameterize again if process data change. They are adapted by recalculating and assigning new parameters to the transmitter or, in the case of the version orifice plate with annular chamber, by using a new orifice disk.

    Опции

    Further versions that are available on request:

    • Other types of primary differential pressure device: orifice plates without support rings, measurement flange orifice plates, venturi nozzles, classic venturi tubes etc.
    • Other nominal diameters and nominal pressures to EN and ASME
    • Other lengths, special lengths
    • Other materials
    • Sealing face with recess or groove
    • Flushing rings
    • Other tapping sockets, multiple tappings
    • Material acceptance test certificates or cold water pressure tests

    Технические данные

    The technical properties of the orifice plates depend on the device:

    • Nominal diameters
    • Nominal pressure
    • Materials
    • Mass
    • Temperature limits

    Дополнительно

    • Compensation vessels
    • Threaded flange pairs
    • Primary shut-offs
    • Valve manifold
    • Differential pressure lines (to be provided by the plant owner)
    • Gaskets, bolts, screws (to be provided by the plant owner)
    • Differential pressure transmitter

    Дальнейшая информация

    • Standards
    • Instruction Manual SITRANS P
    • Installation Instructions