    The basic unit handles the central functions of the SIPLUS HCS300I heating controller and communicates with the higher-level automation system.

    Особенности

    • Three digital relay outputs for switching ohmic loads
    • Communication with the higher-level automation system over PROFIBUS DP
    • Local control of the system
    • Four digital inputs for supplying external signals

    Технические данные

    Order number

     

    6BK1700-3BA20-0AA0

    product brand name

     

    SIPLUS

    Product designation

     

    HCS300I basic device

    Inputs/ Outputs:

     

     

    Type of voltage of output voltages

     

    DC

    Output voltage

    V

    24 ... 125

    Property of the output Short-circuit proof

     

    No

    Output current at digital output for signal <1> maximum

    A

    2

    Galvanic isolation between the outputs and system interface

     

    Yes

    General technical data:

     

     

    Equipment marking acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750

     

    F

    Equipment marking acc. to DIN EN 61346-2

     

    F

    Number of status displays

     

    3

    Display version as status display by LED

     

    device: 4 states, BUS: 2 states, GEN.FAULT: 2 states

    Communication:

     

     

    Design of the interface

     

    PROFIBUS DP

    Ambient conditions:

     

     

    Protection class IP

     

    IP20

    Shock resistance acc. to IEC 60068-2-27

     

    15g / 11 ms

    Conducted interference

     

     

    • due to burst acc. to IEC 61000-4-4

     

    2 kV power supply lines / 1 kV signal lines

    • due to surge acc. to IEC 61000-4-5

     

    on supply cables: 1 kV symmetrical, 2 kV asymmetrical; on signal cables > 30 m unshielded: 1 kV symmetrical, 2 kV asymmetrical, > 30 m unshielded: 2 kV asymmetrical

    • due to high-frequency radiation acc. to IEC 61000-4-6

     

    10 V (0.15 ... 80 MHz)

    Electrostatic discharge acc. to IEC 61000-4-2

     

    6 kV contact discharge / 8 kV air discharge

    Field-bound parasitic coupling acc. to IEC 61000-4-3

     

    10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz)

    EMC emitted interference

     

    IEC61131: Class A; conducted and radiated: DIN EN 55011/CISPR11 (corresponds to degree of severity A)

    Installation altitude at height above sea level maximum

    m

    2 000

    Ambient temperature

     

     

    • during storage

    °C

    -40 ... +80

    • during operation

    °C

    -25 ... +60

    • during transport

    °C

    -40 ... +80

    Air pressure

     

     

    • during operation

    hPa

    795 ... 1 080

    • during storage

    hPa

    660 ... 1 080

    Connections:

     

     

    Type of switching output

     

    monostable relays

    Type of electrical connection for auxiliary and control current circuit

     

    screw-type terminals

    Installation/ mounting/ dimensions:

     

     

    Mounting position

     

    any

    Mounting type

     

    Snap-mounting on a TH 35 mm standard rail compliant with IEC 60715 or screw-mounted using additional push-in lug

    Width

    mm

    45

    Height

    mm

    106

    Depth

    mm

    115

    Certificates/ approvals:

     

     

    Certificate of suitability

     

    CE, cULus, C-Tick (RCM)