Line-side components - Recommended fuses

  • Информационные материалы

    Информационные материалы

    The fuses specified below are the recommended types for protecting the unit on the low-voltage distribution panel. If option L26 was selected for SINAMICS S150 with rated input currents <800 A, then the semiconductor protection is already integrated in the unit. For units of >800 A, this function is performed by the circuit breaker provided as standard.
    In this case, a 3NA fuse can be used in the distribution board. If option L26 has not been selected for units <800 A, we strongly advise that 3NE fuses are used 1).

    Catalog LV 10 contains additional information on the listed fuses.

    Type rating
    at 400 V or 690 V

    SINAMICS S150 converter

    Cable protection fuse
    in systems with a fuse switch disconnector

    Cable protection fuse
    (incl. semiconductor protection)
    in systems without fuse switch disconnector

    At IL, 50 Hz 400 V, 500 V or 690 V

    At IL, 60 Hz 460 V or 575 V

     

     

    Rated current

    Size according to DIN 43620‑1

     

    Rated current

    Size according to DIN 43620‑1

    kW

    hp

    6SL3710-...

    Article No.

    A

     

    Article No.

    A

     

    Line voltage 380 ... 480 V 3 AC

    110

    150

    7LE32-1AA3

    3NA3252

    315

    2

    3NE1230-2

    315

    1

    132

    200

    7LE32-6AA3

    3NA3254

    355

    2

    3NE1331-2

    350

    2

    160

    250

    7LE33-1AA3

    3NA3365

    500

    3

    3NE1334-2

    500

    2

    200

    300

    7LE33-8AA3

    3NA3365

    500

    3

    3NE1334-2

    500

    2

    250

    400

    7LE35-0AA3

    3NA3372

    630

    3

    3NE1436-2

    630

    3

    315

    500

    7LE36-1AA3

    3NA3475

    800

    4

    3NE1438-2

    800

    3

    400

    600

    7LE37-5AA3

    3NA3475

    800

    4

    3NE1448-2

    850

    3

    450

    700

    7LE38-4AA3

    Circuit breaker included as standard

    560

    800

    7LE41-0AA3

    Circuit breaker included as standard

    710

    1000

    7LE41-2AA3

    Circuit breaker included as standard

    800

    1000

    7LE41-4AA3

    Circuit breaker included as standard

    Line voltage 500 ... 690 V 3 AC

    75

    75

    7LG28-5AA3

    3NA3132-6

    125

    1

    3NE1022-2

    125

    00

    90

    75

    7LG31-0AA3

    3NA3132-6

    125

    1

    3NE1022-2

    125

    00

    110

    100

    7LG31-2AA3

    3NA3136-6

    160

    1

    3NE1224-2

    160

    1

    132

    150

    7LG31-5AA3

    3NA3240-6

    200

    2

    3NE1225-2

    200

    1

    160

    150

    7LG31-8AA3

    3NA3244-6

    250

    2

    3NE1227-2

    250

    1

    200

    200

    7LG32-2AA3

    3NA3252-6

    315

    2

    3NE1230-2

    315

    1

    250

    250

    7LG32-6AA3

    3NA3354-6

    355

    3

    3NE1331-2

    350

    2

    315

    300

    7LG33-3AA3

    3NA3365-6

    500

    3

    3NE1334-2

    500

    2

    400

    400

    7LG34-1AA3

    3NA3365-6

    500

    3

    3NE1334-2

    500

    2

    450

    450

    7LG34-7AA3

    3NA3352-6

    2 × 315

    2

    3NE1435-2

    560

    3

    560

    600

    7LG35-8AA3

    3NA3354-6

    2 × 355

    3

    3NE1447-2

    670

    3

    710

    700

    7LG37-4AA3

    3NA3365-6

    2 × 500

    3

    3NE1448-2

    850

    3

    800

    800

    7LG38-1AA3

    Circuit breaker included as standard

    900

    900

    7LG38-8AA3

    Circuit breaker included as standard

    1000

    1000

    7LG41-0AA3

    Circuit breaker included as standard

    1200

    1250

    7LG41-3AA3

    Circuit breaker included as standard



    1) The double function fuses (3NE1.) with duty class gS for cable and semiconductor protection are recommended to protect the converter. These fuses are specially adapted to the requirements of the semiconductors in the input rectifier.