Товаров
  
корзина пуста
  • Каталог оборудования Siemens

CPU 1516F-3 PN/DP

  • Заказные данные
    (1)
  • Аксессуары
    (41)
  • Информационные материалы

    Информационные материалы

    • The CPU with a large program and data memory in the SIPLUS S7-1500 controller product range for failsafe applications with high requirements regarding program scope and networking.
    • Can be used for failsafe functions up to SIL 3 according to IEC 61508 and up to PLe according to ISO 13849.
    • High processing speed for binary and floating-point arithmetic
    • Used as central controller in production lines with central and distributed I/O.
    • Supports PROFIsafe in centralized and distributed configuration. 
    • PROFINET IO IRT interface with 2-port switch.
    • Additional PROFINET interface with separate IP address.
    • PROFINET IO controller for operating distributed I/O on PROFINET.
    • PROFINET I-Device for connecting the CPU as an intelligent PROFINET device under a SIMATIC or non-Siemens PROFINET IO controller.
    • PROFIBUS DP master interface.
    • Isochronous mode on PROFIBUS and PROFINET.
    • Integrated Motion Control functionalities for controlling speed-controlled and positioning axes, support for external encoders.
    • Integrated Web server with the option of creating user-defined Web pages.

    Note:

    SIMATIC memory card required for operation of the CPU

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the corresponding standard products. SIPLUS extreme-specific information was added.

    Область применения

    The CPU 1516F-3 PN/DP is the CPU with a large program and data memory for demanding standard and fail-safe applications that also contain distributed automation structures alongside central I/O.

    It can be used as a PROFINET IO Controller or as distributed intelligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as a 2-port switch so that a linear topology can be set up in the system. The additional integrated PROFINET interface with separate IP address can be used, for example, for network separation. Distributed I/O can be connected via PROFIBUS (or PROFIsafe) via the integrated PROFIBUS interface. In addition, the CPU offers comprehensive control functionalities as well as the ability to connect drives via standardized PLC-open blocks.

    Дизайн

    The CPU 1516F-3 PN/DP has:

    • a powerful processor:
      The CPU achieves a command execution time as low as 10 ns per binary command.
    • extensive RAM:
      1.5 MB for program, 5 MB for data
    • SIMATIC Memory Cards as load memory;
      permit additional functions such as datalog and archives
    • Flexible expansion possibilities:
      single-tier configuration with max. 32 modules (CPU + 31 modules)
    • Display with functions for:
      • displaying overview information such as IP address of the integrated interface, station name, plant designation, location identifier, etc.
      • displaying safety mode, overall signature and date of the last download with signature change
      • Display of diagnostic information
      • Display of module information
      • Showing display settings
      • Display of a user-definable logo
      • Setting IP addresses
      • Setting of date and time
      • Selection of operating mode
      • Resetting of the CPU to factory settings
      • Disabling/enabling of display
      • Enabling of protection levels
      • Display of safety mode, overall signature and date of the last download with signature change.
    • PROFINET IO IRT interface for connecting distributed I/O via PROFINET
    • PROFINET interface for network separation
    • PROFIBUS DP interface for connecting distributed I/O via PROFIBUS
    • Supports PROFIsafe in centralized and distributed configuration

    Функции

    Thanks to a variety of innovations and integrated functions, the SIMATIC S7-1500 CPUs offer added value with regard to performance and engineering efficiency. A host of features support users in programming, commissioning, and servicing the S7-1500:

    • Performance
      • Faster command processing, depending on the CPU type, language extensions and new data types
      • Even shorter response times of the CPUs due to considerably faster backplane bus
      • High-performance network connection:
        PROFINET IO IRT (2-port switch) as standard interface. Additional PROFINET interface integrated, e.g. for network separation.
    • Integrated technology
      • Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
      • Support of speed-controlled and positioning axes as well as external encoders
      • Trace functions for all CPU tags, both for diagnostics in real time as well as for sporadic error detection
      • Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control parameters for optimum control quality
    • Security Integrated
      • Password-based know-how protection against unauthorized reading and modification of program blocks
      • Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card:
        The block can only run if the configured memory card is inserted in the CPU.
        4-level authorization concept:
        Communication to the HMI devices can also be restricted.
      • Manipulation protection:
        The controller recognizes changed or unauthorized transmissions of the engineering data.
    • Design and handling
      • Display of overview information:
        e.g. station name, plant identifier, location ID, diagnostic information, module information, display settings, etc.
      • Possible operations on the display:
        set addresses, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels.
    • Integrated system diagnostics
      • System diagnostics information is displayed consistently and in plain text in the display, TIA Portal, HMI devices and Web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
      • Integrated in the firmware of the CPU, no special configuration is required
    • SIMATIC Memory Card (required for operation of the CPU)
      • Used as plug-in load memory or for updating the firmware.
      • Also for storing additional documents or csv files (for recipes and archives)
      • Creation of data blocks for storage/reading of data via SFCs of the user program
    • Datalog (archives) and recipes
      • Storage of csv files for recipes and archives on the SIMATIC Memory Card;
        easy access to plant-relevant operating data using Office tools or via a Web server
      • Easy access to configuration data of the machine by means of a Web browser or SD card reader (two-way data exchange from and to the controller)
    • Programming of the standard program section
      • Programming with STEP 7 V13
    • Programming of the failsafe program section
      • Programming of the safety-related program section with the option package "STEP 7 Safety Advanced".

    Технические данные

    Order number

    6AG1516-3FN01-2AB0

    SIPLUS S7-1500 CPU-1516F-3 PN/DP

    General information

     

    Product type designation

    CPU 1516F-3 PN/DP

    Engineering with

     

    • STEP 7 TIA Portal configurable/integrated as of version

    V13 SP1 Update 4

    Supply voltage

     

    Type of supply voltage

    24 V DC

    Power loss

     

    Power loss, typ.

    7 W

    Memory

     

    Work memory

     

    • integrated (for program)

    1.5 Mbyte

    • integrated (for data)

    5 Mbyte

    Load memory

     

    • Plug-in (SIMATIC Memory Card), max.

    32 Gbyte

    CPU processing times

     

    for bit operations, typ.

    10 ns

    for word operations, typ.

    12 ns

    for fixed point arithmetic, typ.

    16 ns

    for floating point arithmetic, typ.

    64 ns

    Counters, timers and their retentivity

     

    S7 counter

     

    • Number

    2 048

    IEC counter

     

    • Number

    Any (only limited by the main memory)

    S7 times

     

    • Number

    2 048

    IEC timer

     

    • Number

    Any (only limited by the main memory)

    Data areas and their retentivity

     

    Flag

     

    • Number, max.

    16 kbyte

    Address area

     

    I/O address area

     

    • Inputs

    32 kbyte; All inputs are in the process image

    • Outputs

    32 kbyte; All outputs are in the process image

    Time of day

     

    Clock

     

    • Type

    Hardware clock

    1. Interface

     

    Interface types

     

    • Number of ports

    2

    • integrated switch

    Yes

    • RJ 45 (Ethernet)

    Yes; X1

    Functionality

     

    • PROFINET IO Controller

    Yes

    • PROFINET IO Device

    Yes

    • SIMATIC communication

    Yes

    • Open IE communication

    Yes

    • Web server

    Yes

    • Media redundancy

    Yes

    2. Interface

     

    Interface types

     

    • Number of ports

    1

    • integrated switch

    No

    • RJ 45 (Ethernet)

    Yes; X2

    Functionality

     

    • PROFINET IO Controller

    No

    • PROFINET IO Device

    No

    • SIMATIC communication

    Yes

    • Open IE communication

    Yes

    • Web server

    Yes

    3. Interface

     

    Interface types

     

    • Number of ports

    1

    • RS 485

    Yes

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    No

    • SIMATIC communication

    Yes

    Protocols

     

    Supports protocol for PROFINET IO

    Yes

    PROFIsafe

    Yes

    PROFIBUS

    Yes

    Number of connections

     

    • Number of connections, max.

    256; via integrated interfaces of the CPU and connected CPs / CMs

    PROFINET IO Controller

     

    Services

     

    • Number of connectable IO Devices, max.

    256; In total, up to 768 distributed I/O devices can be connected via PROFIBUS or PROFINET

    • Of which IO devices with IRT, max.

    64

    • Number of connectable IO Devices for RT, max.

    256

    PROFIBUS DP master

     

    Services

     

    • Number of DP slaves

    125; In total, up to 768 distributed I/O devices can be connected via PROFIBUS or PROFINET

    Isochronous mode

     

    Isochronous operation (application synchronized up to terminal)

    Yes; With minimum OB 6x cycle of 375 µs

    Supported technology objects

     

    Motion Control

    Yes

    • Speed-controlled axis

    • Number of speed-controlled axes, max.

    30; Requirement: There must be no other motion technology objects created

    • Positioning axis

    • Number of positioning axes, max.

    30; Requirement: There must be no other motion technology objects created

    • Synchronized axes (relative gear synchronization)

    • Number of axes, max.

    15; Requirement: There must be no other motion technology objects created

    • External encoders

    • Number of external encoders, max.

    30; Requirement: There must be no other motion technology objects created

    Controller

    • PID_Compact

    Yes; Universal PID controller with integrated optimization

    • PID_3Step

    Yes; PID controller with integrated optimization for valves

    • PID-Temp

    Yes; PID controller with integrated optimization for temperature

    Counting and measuring

    • High-speed counter

    Yes

    Ambient conditions

     

    Ambient temperature during operation

     

    • horizontal installation, min.

    -25 °C; = Tmin; startup @ -25 °C; startup display @ -20 °C

    • horizontal installation, max.

    60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off

    • vertical installation, min.

    -25 °C; = Tmin; startup @ -25 °C; startup display @ -20 °C

    • vertical installation, max.

    40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Configuration

     

    Programming

     

    Programming language

     

    • LAD

    Yes; incl. failsafe

    • FBD

    Yes; incl. failsafe

    • STL

    Yes

    • SCL

    Yes

    • GRAPH

    Yes

    Know-how protection

     

    • User program protection/password protection

    Yes

    • Copy protection

    Yes

    • Block protection

    Yes

    Access protection

     

    • Password for display

    Yes

    • Protection level: Write protection

    Yes

    • Protection level: Read/write protection

    Yes

    • Protection level: Complete protection

    Yes

    Dimensions

     

    Width

    70 mm

    Height

    147 mm

    Depth

    129 mm

    Weights

     

    Weight, approx.

    845 g

    Other

     

    Note:

    At temperatures below 0 °C legibility may be restricted and representation of dynamic contents may be slower


    Дальнейшая информация

    Further information and downloads
    Safety Integrated

    Information on functional safety, also for S7-1500F Controllers:

    http://www.siemens.com/safety-integrated

    Manuals

    The SIMATIC S7-1500 manuals can be downloaded free of charge from the Internet (SIMATIC Customer Support, http://www.siemens.com/automation/support).

    General information

    http://www.siemens.com/S7-1500

    SIMATIC Selection Tool

    http://www.siemens.com/tia-selection-tool

    Brochures

    Information material for downloading can be found on the Internet:

    http://www.siemens.com/simatic/printmaterial