Recommended line-side power components

  • Заказные данные
    (32)
  • Информационные материалы

    Информационные материалы

    Selection and ordering data

    The table below lists recommended ratings for input-end switching and fuse protection elements for compliance with IEC standards.

    Notes for use in compliance with IEC standards:

    3NA3 or 3NE1 fuses are recommended for European countries.

    Notes for use in compliance with UL regulations:

    UL-approved fuses must be used in North America.

    • Examples of fuses:
      • Class J and class L fuses, supplied by Cooper Bussmann

    Additional information about the listed fuses can be found in Catalogs LV 10, IC 10 and IC 10 AO.

    Rated power 1)

    SINAMICS G120
    PM330 Power Modules

    Main contactor acc. to IEC

    Switch disconnector acc. to IEC

    Cable protection fuse
    incl. Solid-state contactor2)

    IEC-compliant

    Cable protection fuse acc. to IEC

    Cable protection fuse

    acc. to UL/cUL,
    Class J/L

    400 V/690 V

    460 V/575 V

    Type

     

     

    Rated current

     

    Rated current

    Minimum short-circuit current

     

    Rated current

    Minimum short-circuit current

     

    Rated current

     

    kW

    hp

    6SL3310-...

    Frame size

    Type

    A

    Type

    A

    A

    Article No.

    A

    A

    Article No.

    A

    Reference No. 3)
    or
    Article No.

    380 ... 480 V 3 AC

    160

    200

    1PE33-0AA0

    GX

    3RT1456
    (2 units)

    400

    3KL5730

    450

    4400

    3NE1333-2

    400

    9500

    3NA3260

    400

    DFJ-400
    Class J

    200

    250

    1PE33-7AA0

    GX

    3RT1456
    (2 units)

    400

    3KL5730

    500

    5200

    3NE1334-2

    500

    14000

    3NA3365

    500

    DFJ-500
    Class J

    250

    300

    1PE34-6AA0

    GX

    3RT1456
    (3 units)

    630

    3KL6130

    560

    7000

    3NE1435-2

    630

    20000

    3NA3372

    600

    DFJ-600
    Class J

    315

    400

    1PE35-8AA0

    HX

    3RT1456
    (3 units)

    630

    3KL6130

    710

    10000

    3NE1437-2

    650

    KTU650
    Class L

    355

    450

    1PE36-6AA0

    HX

    3RT1466
    (2 units)

    800

    3KL6230

    800

    11000

    3NE1438-2

    800

    30000

    3NA3475

    700

    KTU700
    Class L

    400

    500

    1PE37-4AA0

    HX

    3RT1466
    (3 units)

    800

    3KL6230

    850

    13000

    3NE1448-2

    800

    KTU800
    Class L

    450

    500

    1PE38-4AA0

    JX

    3RT1466
    (3 units)

    1000

    3KD5034

    2 × 500

    10400

    3NE1334-3

    (2 units)

    1000

    40000

    3NA3480

    1000

    3NB3350-1KK26

    500

    600

    1PE38-8AA0

    JX

    3RT1466
    (3 units)

    1000

    3KD5034

    2 × 560

    14000

    3NE1435-3

    (2 units)

    1000

    40000

    3NA3480

    1100

    3NB3351-1KK26

    560

    700

    1PE41-0AA0

    JX

    3RT1476
    (2 units)

    1250

    3KD5234

    2 × 630

    16000

    3NE1436-3

    (2 units)

    1250

    52000

    3NA3482

    1250

    3NB3352-1KK26

    500 ... 690 V 3 AC

    500

    500

    1PG35-8AA0

    JX

    3RT1466
    (3 units)

    630

    3KD4634

    710

    10000

    3NE1437-2

    2 x 355

    16000

    3NA3354-6

    710

    3NE1437-2

    560 (751)

    600

    1PG36-5AA0

    JX

    3RT1466
    (3 units)

    800

    3KD4834

    800

    11000

    3NE1438-2

    2 x 400

    20000

    3NA3360-6

    800

    3NE1438-2

    630

    700

    1PG37-2AA0

    JX

    3RT1466
    (3 units)

    1000

    3KD5034

    850

    13000

    3NE1448-2

    2 x 425

    21000

    3NA3362-6

    850

    3NE1448-2



    1) Rated power based on the rated output current Irated.

    2) Suitable for 3KL/3KD switch disconnector.

    3) Recommendation: Class J or class L fuse supplied by Cooper Bussmann.

    Note:

    Important! Note the minimum short-circuit current required to trip the protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.