Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS S7-400 SM 432

  • Заказные данные
    (1)
  • Аксессуары
    (9)
  • Информационные материалы

    Информационные материалы

    • Analog outputs for SIMATIC S7-400
    • For connection of analog actuators
    Note:

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Technical documentation on SIPLUS can be found here:
    http://www.siemens.de/siplus-extreme

    Область применения

    Analog output modules permit the output of analog signals from the controller to the process.

    Дизайн

    The analog output module features the following mechanical characteristics:

    • Compact design:
      The rugged plastic enclosure contains:
      • Labeling strips
      • Easy installation.
    • User-friendly wiring:
      The modules are wired via a plug-in front connector.
    • Different measurement ranges.

    Функции

    The analog output modules convert digital values from the S7-400 into analog signals for the process.

    Технические данные

    Order number

    6AG1432-1HF00-4AB0

    SIPLUS_SM432_8AA

    Supply voltage

     

    Load voltage L+

     

    • Rated value (DC)

    24 V

    • Reverse polarity protection

    Yes

    Input current

     

    from supply voltage L+, max.

    400 mA

    from backplane bus 5 V DC, max.

    150 mA

    Power loss

     

    Power loss, typ.

    9 W

    Analog outputs

     

    Number of analog outputs

    8

    Voltage output, short-circuit protection

    Yes

    Voltage output, short-circuit current, max.

    30 mA

    Current output, no-load voltage, max.

    19 V

    Output ranges, voltage

     

    • 0 to 10 V

    Yes

    • 1 V to 5 V

    Yes

    • -10 V to +10 V

    Yes

    Output ranges, current

     

    • 0 to 20 mA

    Yes

    • -20 mA to +20 mA

    Yes

    • 4 mA to 20 mA

    Yes

    Load impedance (in rated range of output)

     

    • with voltage outputs, min.

    1 kΩ

    • with voltage outputs, capacitive load, max.

    1 µF

    • with current outputs, max.

    500 Ω; 600 ohms if common-mode-voltage reduced to <1 V

    Cable length

     

    • shielded, max.

    200 m

    Analog value generation for the outputs

     

    Integration and conversion time/resolution per channel

     

    • Resolution with overrange (bit including sign), max.

    13 bit

    • Conversion time (per channel)

    420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges

    Settling time

     

    • for resistive load

    0.1 ms

    • for capacitive load

    3.5 ms

    • for inductive load

    0.5 ms

    Errors/accuracies

     

    Operational error limit in overall temperature range

     

    • Voltage, relative to output range, (+/-)

    0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V

    • Current, relative to output range, (+/-)

    1 %; +/-20 mA, 4 to 20 mV

    Basic error limit (operational limit at 25 °C)

     

    • Voltage, relative to output range, (+/-)

    0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V

    • Current, relative to output range, (+/-)

    0.5 %; +/-20 mA, 0 to 20 mA

    Potential separation

     

    Potential separation analog outputs

     

    • between the channels and backplane bus

    Yes

    Isolation

     

    Isolation tested with

    2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground

    Ambient conditions

     

    Ambient temperature during operation

     

    • min.

    0 °C; = Tmin

    • max.

    60 °C; = Tmax

    Ambient temperature during storage/transportation

     

    • min.

    -40 °C

    • max.

    70 °C

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Dimensions

     

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Weights

     

    Weight, approx.

    650 g