Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SM 432 analog output module

  • Заказные данные
    (1)
  • Аксессуары
    (24)
  • Информационные материалы

    Информационные материалы

    • Analog outputs for the SIMATIC S7-400
    • For the connection of analog actuators

    Область применения

    Analog output modules can be used to output analog signals from the control to the process.

    Дизайн

    The analog output module is characterized by the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains:
      • Labeling strips
    • Simple assembly
    • User-friendly wiring:
      The modules are wired by means of a plug-in front connector.
    • Different measurement ranges

    Функции

    Analog output modules convert digital values from the S7-400 into analog signals for the process.

    Технические данные

    Order number

    6ES7432-1HF00-0AB0

    SM 432, 8AO, U/I, 13BIT

    Supply voltage

     

    Load voltage L+

     

    • Rated value (DC)

    24 V

    • Reverse polarity protection

    Yes

    Input current

     

    from supply voltage L+, max.

    400 mA

    from backplane bus 5 V DC, max.

    150 mA

    Power loss

     

    Power loss, typ.

    9 W

    Analog outputs

     

    Number of analog outputs

    8

    Voltage output, short-circuit protection

    Yes

    Voltage output, short-circuit current, max.

    30 mA

    Current output, no-load voltage, max.

    19 V

    Output ranges, voltage

     

    • 0 to 10 V

    Yes

    • 1 V to 5 V

    Yes

    • -10 V to +10 V

    Yes

    Output ranges, current

     

    • 0 to 20 mA

    Yes

    • -20 mA to +20 mA

    Yes

    • 4 mA to 20 mA

    Yes

    Load impedance (in rated range of output)

     

    • with voltage outputs, min.

    1 kΩ

    • with voltage outputs, capacitive load, max.

    1 µF

    • with current outputs, max.

    500 Ω; 600 ohms if common-mode-voltage reduced to <1 V

    Cable length

     

    • shielded, max.

    200 m

    Analog value generation for the outputs

     

    Integration and conversion time/resolution per channel

     

    • Resolution with overrange (bit including sign), max.

    13 bit

    • Conversion time (per channel)

    420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges

    Settling time

     

    • for resistive load

    0.1 ms

    • for capacitive load

    3.5 ms

    • for inductive load

    0.5 ms

    Errors/accuracies

     

    Operational error limit in overall temperature range

     

    • Voltage, relative to output range, (+/-)

    0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V

    • Current, relative to output range, (+/-)

    1 %; +/-20 mA, 4 to 20 mV

    Basic error limit (operational limit at 25 °C)

     

    • Voltage, relative to output range, (+/-)

    0.5 %; +/-10 V, 0 to 10 V, 1 to 5 V

    • Current, relative to output range, (+/-)

    0.5 %; +/-20 mA, 0 to 20 mA

    Potential separation

     

    Potential separation analog outputs

     

    • between the channels and backplane bus

    Yes

    Isolation

     

    Isolation tested with

    2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground

    Dimensions

     

    Width

    25 mm

    Height

    290 mm

    Depth

    210 mm

    Weights

     

    Weight, approx.

    650 g


    Дальнейшая информация

    Brochures

    Information material for downloading can be found in the Internet:

    http://www.automation.siemens.com/infocenter