Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS CM DP for ET 200SP CPU

  • Заказные данные
    (1)
  • Аксессуары
    (12)
  • Информационные материалы

    Информационные материалы

    • PROFIBUS DP master/slave with electrical interface for connecting the ET 200SP CPUs to PROFIBUS at up to 12 Mbit/s
    • Expands the ET 200SP CPUs 1510SP-1 PN / 1512SP-1 PN by one PROFIBUS connection
    • For communication with lower-level PROFIBUS devices at bandwidths of 9.6 kbit/s to 12 Mbit/s
    • Communications services:
      • PROFIBUS DP
      • PG/OP communication
      • S7 communication
        This makes it possible to establish communication between the ET 200SP CPU and other devices, for example those from the SIMATIC S7-300/400/1500 range.
    • Time synchronization
    • Simple programming and configuration over PROFIBUS
    • Cross-network PG communication using S7 routing
    • Data record routing

    Note

    SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

    Область применения

    The CM DP module extends the CPU 1510SP-1 PN / 1512SP-1 PN to include a PROFIBUS DP interface. Which enables either a lower-level or a higher-level PROFIBUS DP line to be established. This has the following advantages:

    • Offloading of the central controller by means of distributed preprocessing
    • CPU 1510SP-1 PN or CPU 1512SP-1 PN possible in standalone mode as DP master

    Communication options of the ET 200SP-CPU via CM DP module:

    • As master for PROFIBUS DP according to IEC 61158/EN 50170 for 125 DP slaves
    • As intelligent DP slave for higher-level DP master on PROFIBUS DP
    • Communication with programming devices and HMI devices
    • Communication with other SIMATIC S7 systems
    • Communication with SIMATIC S5 programmable controllers

    Дизайн

    The CM DP communication module features all the advantages of the ET 200SP design:

    • Compact design:
      • 9-pin D-sub socket for connection to PROFIBUS DP
      • The module is supplied with power via the integrated backplane bus
      • "DIAG" LED for indicating the operational and communication status
    • Simple installation:
      • The CM DP module is snapped onto the DIN rail and connected with the ET 200SP CPU
      • The CM DP module is always to be positioned immediately to the right of the ET 200SP CPU
      • Only one CM DP module can be operated per ET 200SP CPU.
    • User-friendly wiring:
      The D-sub socket is easily accessible and simple to use.

    Функции

    The CM DP module supports the following communication services:

    • PROFIBUS DP Master Class 1
      • PROFIBUS DP (according to IEC 61158/61784)
    • PROFIBUS DP slave
    • PG/OP communication
    • S7 communication
    • Time synchronization via PROFIBUS

    Master for PROFIBUS DP

    The CM DP module operates as a DP-V1 master and processes the data transfer completely independently. It also supports the acyclic standard services, including interrupt handling. During normal operation, it is also possible to activate or deactivate DP slaves. Among other things, this allows the step-by-step commissioning of subprocesses. A diagnostic repeater allows the line to be diagnosed during operation, enabling line faults to be detected at an early stage. The CM DP module supports operation with a diagnostic repeater (including activation of topology identification on the diagnostic repeater).

    It is possible to connect PROFIBUS slaves, e.g. CM 1242-5 as a DP slave, DP slaves of the ET 200 distributed I/O, etc.

    This creates the possibility for the ET 200SP CPU of setting up a further distributed I/O in addition to the network of the integrated PROFINET interface.

    DP slave for PROFIBUS DP

    The CM DP module operates as a DP slave and processes the data transfer completely independently. It thus connects the ET 200SP CPU as intelligent slave to a higher-level DP master.

    This creates the possibility for the ET 200SP CPU being connected to an existing PROFIBUS DP network as intelligent slave in addition to the network of the integrated PROFINET interface.

    The CM DP module can be operated as DP slave on the following DP masters:

    • SIMATIC S7-1200, S7-300, S7-400, S7-1500
    • ET 200 CPUs and CPs with one DP master interface
    • Third-party systems with PROFIBUS DP master interface (via a GSD file).

    PG/OP communication

    PG/OP communication allows all S7 stations connected to the network to be remotely programmed.

    • S7 routing: With the aid of routing it is possible to use programming device communication across different networks.

    S7 communication

    S7 communication is used for the coupling

    • between SIMATIC S7 automation systems
    • and programming devices (PG/OP communication)
    • to PCs, e.g. CP 5711 with SOFTNET-PB S7, CP 5623 etc.
    • and HMI devices (OPs).

    Time synchronization

    Time synchronization is used to set the time of day throughout the plant.

    The CM DP module is capable of forwarding the time of day of the ET 200SP CPU to PROFIBUS. Conversely, the CM DP of the CPU can make an existing time on PROFIBUS available.

    Data set routing

    The CM DP module supports the "data record" routing function. With this option, the CM can be used as a router for data records that need to be sent to field devices (DP slaves). Data records from devices that are not connected directly to PROFIBUS and therefore have no direct access to the DP slaves are forwarded to the DP slaves by the CM.

    Diagnostics

    • Connection diagnostics
    • Support of operation with diagnostic repeater
    • "DIAG" LED for indicating the operational and communication status

    Configuration

    STEP 7 Professional V13, Update 3 (TIA Portal) or higher is required for configuring the full range of functions of the CM DP module. The configuration data of the CM is always saved on the CPU and retained even after a PLC failure. It is therefore possible to replace a module without having to reload the configuration data from a programming device.

    A prerequisite for the DP Slave functionality is FW V1.7 of the ET 200SP CPU or higher.

    Configuration and programming of all SIMATIC S7 controllers connected to the network is possible over the network.

    Технические данные

    Order number

    6AG1545-5DA00-2AB0

    SIPLUS ET 200SP CM DP

    General information

     

    Product type designation

    ET 200SP, CM DP

    Supply voltage

     

    Type of supply voltage

    24 V DC

    Rated value (DC)

    24 V

    permissible range, lower limit (DC)

    19.2 V

    permissible range, upper limit (DC)

    28.8 V

    Reverse polarity protection

    Yes

    1. Interface

     

    Interface types

     

    • RS 485

    Yes

    Functionality

     

    • PROFIBUS DP master

    Yes

    • PROFIBUS DP slave

    Yes

    • SIMATIC communication

    Yes

    RS 485

     

    • Transmission rate, max.

    12 Mbit/s

    • Cable length, max.

    100 m

    Protocols

     

    PROFIBUS DP master

     

    Services

     

    • PG/OP communication

    Yes

    • S7 routing

    Yes

    • Data record routing

    Yes

    • Isochronous mode

    No

    • Equidistance

    No

    • Number of DP slaves

    125

    • Activation/deactivation of DP slaves

    Yes

    PROFIBUS DP slave

     

    • Transmission rate, max.

    12 Mbit/s

    • automatic baud rate search

    Yes

    • Address area, max.

    120

    • User data per address area, max.

    128 byte

    Services

     

    • PG/OP communication

    Yes; Only with active interface

    • Routing

    Yes; Only with active interface

    • S7 communication

    Yes; Only with active interface

    • Direct data exchange (slave-to-slave communication)

    Yes; No subscriber possible - only passive publisher

    • DPV1

    Yes

    Transfer memory

     

    • Inputs

    244 byte

    • Outputs

    244 byte

    Interrupts/diagnostics/status information

     

    Diagnostics function

    Yes

    Diagnostics indication LED

     

    • for module diagnostics

    Yes; green/red DIAG LED

    Potential separation

     

    between backplane bus and interface

    Yes

    Ambient conditions

     

    Ambient temperature during operation

     

    • horizontal installation, min.

    -40 °C; = Tmin; Startup @ -25 °C

    • horizontal installation, max.

    60 °C; = Tmax

    • vertical installation, min.

    -40 °C; = Tmin; Startup @ -25 °C

    • vertical installation, max.

    50 °C; = Tmax

    Extended ambient conditions

     

    • relative to ambient temperature-atmospheric pressure-installation altitude

    Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

    Relative humidity

     

    • With condensation, tested in accordance with IEC 60068-2-38, max.

    100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

    Resistance

     

    • against biologically active substances / conformity with EN 60721-3-3

    Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

    • against chemically active substances / conformity with EN 60721-3-3

    Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances / conformity with EN 60721-3-3

    Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

    Dimensions

     

    Width

    35 mm

    Height

    117 mm

    Depth

    75 mm

    Weights

     

    Weight, approx.

    80 g


    Дальнейшая информация

    Further information and downloads

    Manuals

    The ET 200SP manuals can be downloaded free of charge from the Internet (SIMATIC Customer Support).
    http://support.automation.siemens.com/WW/view/en/84133942

    General information

    http://www.siemens.com/et200sp

    SIMATIC Selection Tool

    http://www.siemens.com/tia-selection-tool

    Brochures

    Information material for downloading can be found on the Internet:

    http://www.siemens.com/simatic/printmaterial