Товаров
  
корзина пуста
  • Каталог оборудования Siemens

SIPLUS Power Modules

  • Заказные данные
    (4)
  • Информационные материалы

    Информационные материалы

    Power Modules PM240‑2 – 0.55 kW to 15 kW, IP20 degree of protection

    SINAMICS G120, FSA - FSC, PM230 and PT

    Power Modules PM240‑2, frame sizes FSA to FSF (with control unit and operator panel)

    SINAMICS G120, FSA - FSC, PM230 and PT

    Power Modules PM240‑2, IP20 degree of protection, push-through version, frame sizes FSA to FSC (with control unit and operator panel)

    The new PM240‑2 Power Modules are based on a new hardware platform. This permits an increase in power density as well as the application of innovative cooling concepts (push-through technology) with especially high requirements in terms of control cabinet cooling.

    Furthermore, the PM240-2 Power Module is also suitable for use in safety-oriented applications. In conjunction with a fail-safe control unit, the drive can be turned into a Safety Integrated Drive. The PM240‑2 Power Module frame sizes FSA to FSC are available both with and without an integrated line filter class A of compact design for 200 V and 400 V line voltages. The PM240-2 Power Modules with integrated line filter class A are suitable for connection to TN supply systems. Power Modules without an integrated line filter can be connected to grounded TN/TT systems and non-grounded IT systems.

    The cable lengths permitted between converter and motor are limited. Longer cables can be used if output reactors are connected.

    Push-through version

    The push-through version allows the cooling fins of the Power Module to be pushed through the rear panel of the control cabinet. Push-through versions should be used in applications in which the amount of waste heat generated inside the control cabinet itself must be minimized.

    Shield plates and shield connection kits are available for use when wiring control units and power modules to ensure compliance with EMC guidelines.

    Note:

    SIPLUS extreme products are based on SINAMICS standard products. The contents listed here were taken from the corresponding standard products. SIPLUS extreme-specific information was added.

    Технические данные

    Order number

     

    6AG1210-1PE14-2UL1

    6AG1210-1PE18-2UL1

    6AG1210-1PE21-2UL0

    6AG1210-1PE23-2UL0

    product brandname

     

    SIPLUS

    Product designation

     

    Power unit

    General technical data:

     

     

     

     

     

    Design of the product

     

    PM240-2

    Vibration frequency during transport acc. to EN 60721-3-2 Note

     

    Class 2M3

    Shock acceleration during operation acc. to EN 60068-2-27

    m/s²

    147

    Power factor

     

    0.85

    Brake version

     

    DC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional)

    Protection function parameter lock

     

    Yes

    Electrical output frequency

    Hz

    50

    Consumed current from supply voltage for Control Unit at DC at 24 V

    A

    1

    Phase number of the output voltage

     

    3

    Input current

     

     

     

     

     

    • ● with low overload rated value

    A

    5.5

    10.1

    22.2

    39.9

    • ● with high overload rated value

    A

    4.7

    8.8

    19.8

    36

    Output current

     

     

     

     

     

    • ● rated value maximum

    A

    6.2

    11.8

    27

    52

    • ● without overload rated value

    A

    4.1

    7.7

    18

    32

    • ● with low overload rated value

    A

    4.1

    7.7

    18

    32

    • ● with high overload rated value

    A

    3.1

    5.9

    13.2

    26

    Supplied active power at rated value of output voltage

     

     

     

     

     

    • ● with low overload

    kW

    1.5

    3

    7.5

    15

    • ● with high overload

    kW

    1.1

    2.2

    5.5

    11

    Efficiency

     

    0.96

    0.97

    Cooling air flow

    m³/s

    0.005

    0.0092

    0.019

    1 m measuring surface sound pressure level maximum

    dB

    50

    62

    65

    Type of electrical connection

     

     

     

     

     

    • ● for PE conductor

     

    Plug-in screw terminals

    • ● for mains supply line

     

    Plug-in screw terminals

    • ● of the motor

     

    Plug-in screw terminals

    Connectable conductor cross-section for mains supply line

     

    1 ... 2.5

    1.5 ... 2.5

    1.5 ... 6

    6 ... 16

    Connectable conductor cross-section for motor supply line

     

    1 ... 2.5

    1.5 ... 2.5

    1.5 ... 6

    6 ... 16

    Wire length for motor shielded maximum

    m

    50

    Power loss [W] maximum

    kW

    0.07

    0.12

    0.2

    0.37

    Protection class IP

     

    IP20

    Width

    mm

    73

    100

    140

    Height

    mm

    196

    292

    355

    Depth

    mm

    165

    Design of the converter

     

    FSA

    FSB

    FSC

    Net weight

    kg

    1.4

    3

    4.8

    Ambient conditions:

     

     

     

     

     

    Ambient temperature during operation maximum

    °C

    55

    Relative humidity without condensation during operation maximum Note

     

    RH incl. condensation/frost (no commissioning in bedewed state)

    Relative humidity without condensation during operation maximum

    %

    100

    Touch protection acc. to EN 61800-5-1

     

    Assuming use as prescribed

    Operating resource protection class acc. to EN 61800-5-1

     

    Class I (with protective bonding circuit) and Class III (PELV)

    Ambient temperature

     

     

     

     

     

    • ● during storage

     

    -25 ... +55

    • ● during transport

     

    -40 ... +70

    Ambient temperature [°F]

     

     

     

     

     

    • ● during storage

     

    -13 ... +131

    • ● during storage maximum Note

     

    Class 1K3 acc. to EN 60721-3-1

    • ● during transport

     

    -40 ... +158

    • ● during transport maximum Note

     

    Class 2K3 according to EN 60721-3-2

    Degree of pollution

     

    2 according to EN 61800-5-1

    Resistance to biologically active substances conformity acc. to EN 60721-3-3

     

    Yes

    Resistance to biologically active substances

     

    Class 3B2 acc. to EN 60721-3-3, mold and fungal spores (except fauna)

    • ● conformity acc. to EN 60721-3-3 Note

     

    The supplied plug covers must remain in place over the unused interfaces during operation!

    conformity acc. to EN 60721-3-3

     

    Yes

    Resistance to chemically active substances

     

    Class 3C4 acc. to EN 60721-3-3, including salt spray acc. to EN 60068-2-52 (severity level 3)

    • ● conformity acc. to EN 60721-3-3 Note

     

    Compliant with EN 60721-3-3, Class 3C4 incl. salt spray in accordance with EN 60068-2-52 (severity 3); the supplied plug covers must remain in place on the unused interfaces during operation.

    Resistance to mechanically active substances conformity acc. to EN 60721-3-3

     

    No

    Certificate of suitability

     

    CE / TÜV

    Certificate of suitability for CE marking

     

    EMC Directive 2004/108/EC, Low-Voltage Directive 2006/95/EC

    Standard for EMC acc. to EN 61800-3

     

    The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter.

    Product component Line filter

     

    No

    Power Electronics:

     

     

     

     

     

    Type of voltage of the input voltage

     

    AC

    Electrical output frequency

     

     

     

     

     

    • ● for U/f control

     

    0 ... 650

    • ● for vector control

     

    0 ... 200

    Pulse frequency rated value

    kHz

    4

    Output voltage in percent related to the input voltage

     

    0 ... 95

    Type of duty cycle duration

     

     

     

     

     

    • ● with low overload

     

    1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s

    • ● with high overload

     

    1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s

    Type of cooling

     

    Internal air cooling

    Installation altitude at height above sea level without power reduction maximum

    m

    1 000

    Short-time withstand current (SCCR) of the entire control cabinet acc. to UL 508A

    kA

    65

    Protection function

     

     

     

     

     

    • ● undervoltage protection

     

    Yes

    • ● Overvoltage protection

     

    Yes

    • ● Overload protection

     

    Yes

    • ● Ground fault protection

     

    Yes

    • ● Short-circuit protection

     

    Yes

    • ● Stall protection

     

    Yes

    • ● with blocked rotor

     

    Yes

    • ● for motor Temperature monitoring

     

    Yes

    • ● for converter Temperature monitoring

     

    Yes

    Mechanical data:

     

     

     

     

     

    Shock acceleration during operation Note

     

    (15 × g)/11 ms

    Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 maximum Note

     

    constant deflection 0.075 mm

    Vibration frequency with constant deflection during operation acc. to EN 60068-2-6

     

    10 ... 58

    Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 maximum Note

     

    constant acceleration = 9.81 m/s2 (1 × g)

    Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6

     

    58 ... 200