Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Buffer module

  • Заказные данные
    (1)
  • Аксессуары
    (1)
  • Информационные материалы

    Информационные материалы

    The SITOP PSE201U buffer module bypasses short-term power failures lasting a few seconds and can be used with all 24 V power supplies of the SITOP smart or SITOP modular product lines. The buffer module is equipped with maintenance-free capacitors and automatically takes over the 24 V power supply in case of a power supply failure.

    The SITOP DC UPS modules offer protection in the event of extended power failures. The maintenance-free DC UPS with capacitors are able to reliably supply 24 V for several minutes, and the DC UPS with battery modules for several hours.

    Область применения

    With short-term power failures, the load current is backed up without interruption via the buffer module in combination with a SITOP smart or SITOP modular 24 V stabilized power supply.

    Buffer times:

    • 200 ms at 40 A
    • 400 ms at 20 A
    • 800 ms at 10 A

    You can connect up to 8 buffer modules in parallel to extend the buffer time (max. 10 s).

    Дизайн

    The buffer module is connected in parallel to the output of the SITOP smart or SITOP modular power supply. The connection to the power supply takes place via only 2 cables.

    Функции

    Buffering

    In case of a power failure, the buffer module supplies the load current for the 24 V power supply by means of its energy storage units. Maintenance-free capacitors are used as energy storage units.

    Signaling

    The LED on the device signals a supply voltage > 20.5 V.

    Особенности

    • Bridging of short-term power failures in the time range of seconds
    • Totally maintenance-free capacitors as energy storage
    • Short charging times
    • Parallel switching of several buffer modules possible
    • Fast mounting onto standard rail and simple wiring

    Технические данные

    Article No.

    6EP1961-3BA01

    Input/Output

    Stabilized, isolated
    DC voltage

    Rated voltage Uin rated

    24 V DC

    Voltage range

    24 ... 28.8 V

    Control input

    -

    Rated output voltage Uout rated

    Uin – approx. 1 V

    Rated current Iout rated

    40 A

    Mains buffering

    Backup time:

    • With 40 A load current: 200 ms
    • With 20 A load current: 400 ms
    • With 10 A load current: 800 ms
    • With 5 A load current: 1.6 s

    Reduces the backup time by 100 ms in combination with 6EP1 437-3BA10.

    Buffering time, max.

    10 s

    Protection and monitoring

     

    Current limiting, static

    Typ. 40 A

    Short-circuit protection

    Electronically

    Signaling/alarm signals

     

    Status display

    Green LED for "Supply voltage > 20.5 V"

    Signaling

    -

    Safety

     

    Galvanic isolation

    Yes, SELV acc. to EN 60950-1

    Safety class

    Class I

    Safety test

    Yes

    CE marking

    Yes

    UL/cUL (CSA) approval

    UL-Listed (UL 508) File E197259, CSA (CSA C22.2 No. 14, CSA C22.2 No. 107.1)

    Explosion protection

    -

    Degree of protection (EN 60529)

    IP20

    EMC

     

    Emitted interference

    EN 55022 Class B

    Noise immunity

    EN 61000-6-2

    Operating data

     

    Ambient temperature range

    0 ... +60 °C with natural convection

    Transport and storage temperature range

    -40 ... +85°C

    Humidity class

    Climate class 3K3 according to EN 60721, no condensation

    Mechanics

     

    Connections

    One screw-type terminal each for + and - for 0.5 ... 10 mm2
    solid/finely stranded

    Dimensions (W x H x D) in mm

    70 x 125 x 125

    Weight, approx.

    1.2 kg

    Mounting

    Can be snapped onto standard mounting rail EN 60715 35x7.5/15