    Selection and ordering data

    The following table lists recommendations for additional line-side components, such as fuses and circuit breakers. The values in the table take into account the overload capability of the inverter.

    Notes for use in compliance with IEC standards:

    3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL circuit breakers are recommended for European countries.

    Notes for use in compliance with UL regulations:

    UL-listed fuses Class J or 3NE1 with 600 V AC rated voltage (UL-compliant – corresponds to RU) are required for North America.

    Short Circuit Current Rating SCCR

    Short Circuit Current Rating according to UL

    Valid for the use in NEC Article 409 oder UL 508A/508C compliant industrial control cabinets

    • PM240: 65 kA

    Notes regarding installations in Canada:

    Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter:

    • Rated voltage 480 V (phase-phase) and 480 V (phase-ground)
    • Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)

    All overvoltage protection devices used must comply with Canadian standards for industrial installations.

    Additional information about the listed fuses and circuit breakers can be found in Catalogs LV 10.1, IC 10 and IC 10 AO.

    Rated power 1)

    SINAMICS G120
    PM240 Power Modules

    IEC-compliant

    UL/cUL-compliant

     

     

     

     

    Fuse

    Circuit breaker

    Fuse

    Fuse type

    400 V

    460 V

    Type

     

    Current

    Type 3NA3

     

    Type 3NE1 (RU)

    Rated voltage
    600 V AC

    Current

    kW

    hp

    6SL3224-...

    Frame size

    A

    Article No.

    Article No.

    Article No.

    Class

    A

    380 ... 480 V 3 AC

    90

    125

    0BE37-5 . A0

    FSF

    250

    3NA3144

    3VL4731-.DC36-.... *)

    3NE1227-0

    J

    250

    110

    150

    0BE38-8UA0

    FSF

    J

    300

    132

    200

    0BE41-1UA0

    FSF

    3NE1230-0

    J

    400



    1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).

    *) See Catalog LV 10.1 for Article No. supplements.