Товаров
  
корзина пуста
  • Каталог оборудования Siemens

Recommended line-side power components

  • Заказные данные
    (45)
  • Информационные материалы

    Информационные материалы

    Selection and ordering data

    The following table lists recommendations for additional line-side components, such as fuses and circuit breakers. The values in the table take into account the overload capability of the inverter.

    Notes for use in compliance with IEC standards:

    3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL circuit breakers are recommended for European countries.

    Notes for use in compliance with UL regulations:

    UL-listed fuses Class J or 3NE1 with 600 V AC rated voltage (UL-compliant – corresponds to RU) are required for North America.

    Short-Circuit Current Rating SCCR

    (Short Circuit Current Rating) according to UL

    Applies to industrial control panel installations acc. to NEC Article 409 or UL 508A/508C.

    • PM230 IP55 versions: 40 kA (FSA to FSC), 65 kA (FSD to FSF)
    • PM230 IP20 versions: 65 kA

    Notes regarding installations in Canada:

    Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter:

    • Rated voltage 480 V (phase-phase) and 480 V (phase-ground)
    • Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)

    All overvoltage protection devices used must comply with Canadian standards for industrial installations.

    Additional information about the listed fuses and circuit breakers can be found in Catalogs LV 10, IC 10 and IC 10 AO.

    Rated power 1)

    SINAMICS G120P
    PM230 Power Modules
    Degree of protection IP55/UL Type 12

    IEC-compliant

    UL/cUL-compliant

     

     

     

     

    Fuse

    Circuit breaker

    Fuse type
    Rated voltage 600 V AC

    400 V

    460 V

    Type

     

    Current

    Type 3NA3

     

     

    Current

    kW

    hp

    6SL3223-...

    Frame size

    A

    Article No.

    Article No.

    Class

    A

    380 ... 480 V 3 AC

          

    0.37

    0.5

    0DE13-7 . A1

    FSA

    10

    3NA3803

    3RV2011-1CA10

    J

    10

    0.55

    0.75

    0DE15-5 . A1

    FSA

    3RV2011-1DA10

    0.75

    1

    0DE17-5 . A1

    FSA

    3RV2011-1FA10

    1.1

    1.5

    0DE21-1 . A1

    FSA

    3RV2011-1GA10

    1.5

    2

    0DE21-5 . A1

    FSA

    3RV2011-1JA10

    2.2

    3

    0DE22-2 . A1

    FSA

    3RV2011-1KA10

    3

    4

    0DE23-0 . A1

    FSA

    3RV2021-4AA10

    4

    5

    0DE24-0 . A1

    FSB

    16

    3NA3805

    3RV2021-4BA10

    J

    16

    5.5

    7.5

    0DE25-5 . A1

    FSB

    20

    3NA3807

    J

    25 (55.1)

    7.5

    10

    0DE27-5 . A1

    FSB

    25

    3NA3810

    3RV1031-4EA10

    J

    35

    11

    15

    0DE31-1 . A1

    FSC

    35

    3NA3814

    3RV1031-4FA10

    J

    40

    15

    20

    0DE31-5 . A1

    FSC

    50

    3NA3820

    3RV1031-4HA10

    J

    50

    18.5

    25

    0DE31-8AA1

    FSC

    3RV1042-4KA10

    0DE31-8BA0

    FSD

    22

    30

    0DE32-2 . A0

    FSD

    63

    3NA3822

    J

    63

    30

    40

    0DE33-0 . A0

    FSD

    80

    3NA3824

    3RV1042-4MA10

    J

    80

    37

    50

    0DE33-7 . A0

    FSE

    100

    3NA3830

    3VL1712-.DD33-.... *)

    J

    100

    45

    60

    0DE34-5 . A0

    FSE

    125

    3NA3832

    3VL1716-.DD33-.... *)

    J

    125

    55

    75

    0DE35-5 . A0

    FSF

    160

    3NA3836

    3VL3720-.DC36-.... *)

    J

    160 (353)

    75

    100

    0DE37-5 . A0

    FSF

    200

    3NA3140

    3VL3725-.DC36-.... *)

    J

    200

    90

    125

    0DE38-8 . A0

    FSF

    250

    3NA3144

    3VL4731-.DC36-.... *)

    J

    250



    1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).

    *) See Catalog LV 10 for Article No. supplements.

     

    Rated power 1)

    SINAMICS G120
    PM230 Power Modules
    Degree of protection IP20 Standard variant

    IEC-compliant

    UL/cUL-compliant

     

     

     

     

    Fuse

    Fuse

    Fuse type
    Rated voltage 600 V AC

    400 V

    460 V

    Type

     

    Current

    Type 3NE1 (RU)

    Type 3NE1 (RU)

     

    Current

    kW

    hp

    6SL3210-...

    Frame size

    A

    Article No.

    Article No.

    Class

    A

    380 ... 480 V 3 AC

    0.37

    0.5

    1NE11-3 . L1

    FSA

    16

    3NE1813-0

    3NE1813-0

    J

    2

    0.55

    0.75

    1NE11-7 . L1

    FSA

    J

    4

    0.75

    1

    1NE12-2 . L1

    FSA

    1.1

    1.5

    1NE13-1 . L1

    FSA

    J

    6

    1.5

    2

    1NE14-1 . L1

    FSA

    2.2

    3

    1NE15-8 . L1

    FSA

    J

    10

    3

    4

    1NE17-7 . L1

    FSA

    4

    5

    1NE21-0 . L1

    FSB

    J

    15

    5.5

    7.5

    1NE21-3 . L1

    FSB

    20

    3NE1814-0

    3NE1814-0

    J

    20

    7.5

    10

    1NE21-8 . L1

    FSB

    25

    3NE1815-0

    3NE1815-0

    J

    25

    11

    15

    1NE22-6 . L1

    FSC

    35

    3NE1803-0

    3NE1803-0

    J

    35

    15

    20

    1NE23-2 . L1

    FSC

    45

    3NE1817-0

    3NE1817-0

    J

    45

    18.5

    25

    1NE23-8 . L1

    FSC

    50

    J

    50

    22

    30

    1NE24-5 . L0

    FSD

    63

    3NE1818-0

    3NE1818-0

    30

    40

    1NE26-0 . L0

    FSD

    80

    3NE1820-0

    3NE1820-0

    37

    50

    1NE27-5 . L0

    FSE

    100

    3NE1021-0

    3NE1021-0

    45

    60

    1NE28-8 . L0

    FSE

    125

    3NE1022-0

    3NE1022-0

    55

    75

    1NE31-1 . L0

    FSF

    160

    3NE1224-0

    3NE1224-0

    75

    100

    1NE31-5 . L0

    FSF

    200

    3NE1225-0

    3NE1225-0



    1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).

     

    Rated power 1)

    SINAMICS G120
    PM230 Power Modules
    Degree of protection IP20 Push Through variant

    IEC-compliant

    UL/cUL-compliant

     

     

     

     

    Fuse

    Fuse

    Fuse type
    Rated voltage 600 V AC

    400 V

    460 V

    Type

     

    Current

    Type 3NE1 (RU)

    Type 3NE1 (RU)

     

    Current

    kW

    hp

    6SL3211-...

    Frame size

    A

    Article No.

    Article No.

    Class

    A

    380 ... 480 V 3 AC

    3

    4

    1NE17-7 . L1

    FSA

    16

    3NE1813-0

    3NE1813-0

    J

    10

    7.5

    10

    1NE21-8 . L1

    FSB

    25

    3NE1815-0

    3NE1815-0

    J

    25

    18.5

    25

    1NE23-8 . L1

    FSC

    50

    3NE1817-0

    3NE1817-0

    J

    50



    1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).